- Products
- Ground Fault Monitoring, Ungrounded

ISOMETER® isoRW685W-D-B
- Railway
- universally applicable
The ISOMETER® isoRW685W-D-B is an insulation monitoring device for IT systems in accordance with IEC 61557-8 for railway applications and has been specifically tested according to DIN EN 50155. It is universally applicable in AC, 3(N)AC, AC/DC and DC systems. AC systems may include extensive DC-supplied loads (such as rectifiers, converters, variable-speed drives).
- Features
- Applications
- Accessories
- Ordering information
- Downloads
- ISOMETER® for AC IT systems with galvanically connected rectifiers or converters and for DC IT systems (IT = unearthed systems)
- Automatic adaptation to the existing system leakage capacitance
- Combination of AMPPlus and other profiledependent measurement methods
- Two separately adjustable response value ranges of 1 kΩ…10 MΩ
- High-resolution graphic LC display
- Connection monitoring (monitoring of the measuring lines)
- Automatic device self test
- Graphical representation of the insulation resistance over time (isoGraph)
- History memory with real-time clock (buffer for 13 days) for storing a maximum of 1023 alarm messages with date and time
- Current or voltage output 0(4)…20 mA, 0…400 μA, 0…10 V, 2…10 V (galvanically separated) which is analogous to the measured insulation value of the system
- Freely programmable digital inputs and outputs
- Remote setting via the Internet or Intranet (web server/option: COMTRAXX® gateway)
- Remote diagnosis via the Internet (only by Bender service)
- isoData: Continuous uninterrupted data transmission
- RS-485/BS (Bender sensor bus) for data exchange with other Bender devices via Modbus RTU protocol
- BCOM, Modbus TCP und web server
- ISOnet: Internal separation of the ISOMETER® from the IT system to be monitored (e.g. if several IT systems are interconnected)
- ISOnet priority: Permanent priority of a device within the network
- ISOloop: Special function for ring systems (all systems are coupled)
- AC, DC or AC/DC main circuits
- AC/DC main circuits with directly connected DC components, such as rectifiers, converters, variable-speed drives
- UPS systems, battery systems
- Heaters with phase control
- Systems with switch-mode power supplies
- IT systems with high leakage capacitances
Mandatory accessories for ISOMETER® isoRW685W-D-B
Type designation | Art. No. |
---|---|
A set of screw terminals* | B91067901 |
A set of push-wire terminals | B91067902 |
Enclosure accessories (terminal cover, 2 mounting clips)* | B91067903 |
* included in the scope of delivery
Optional accessories for ISOMETER® isoRW685W-D-B
Type designation | Type | Art. No. |
---|---|---|
Coupling devices | AGH150W-4 AGH204S-4 AGH520S AGH676S-4 | B98018006 B914013 B913033 B913055 |
Suitable measuring instruments on request!
Variants of ISOMETER® isoRW685W-D-B
Type | Nominal system voltage range Un | Supply voltage US | Art. No. |
---|---|---|---|
isoRW685W-D-B | AC 0…690 V; 0,1…460 Hz DC 0…1000 V | AC 24…240 V; 50…400 Hz / DC 24…240 V | B91067022W |
Downloads for ISOMETER® isoRW685W-D-B