The isoGEN423 monitors the insulation resistance of ungrounded AC, AC/DC and DC systems with nominal system voltages of 0…400 V. The monitored system can be single-phase AC, 3- or 4-wire AC, AC/DC mixed-phase, or DC.
Automatically adapts to the maximum permissible system-leakage capacitance of 5 μF. DC components existing in AC systems do not influence the operating characteristics, when a minimum load current of DC 10 mA flows. Using a separate supply voltage allows de-energized systems to be monitored.
The isoGEN423 monitors the insulation resistance of ungrounded AC, AC/DC and DC systems with nominal system voltages of 0…400 V. The monitored system can be single-phase AC, 3- or 4-wire AC, AC/DC mixed-phase, or DC.
Automatically adapts to the maximum permissible system-leakage capacitance of 5 μF. DC components existing in AC systems do not influence the operating characteristics, when a minimum load current of DC 10 mA flows. Using a separate supply voltage allows de-energized systems to be monitored.
Type | Version | Art. No. |
---|---|---|
isoGEN423-D4-4 | Push-wire terminal | B71036325 |
isoGEN423-D4W-4 | Push-wire terminal | B71036325W |
Type | Art. No. |
---|---|
Mounting clip for screw mounting (one piece per device) | B98060008 |
Mounting frame XM420 | B990994 |
Category | Name | Size | Language | Timestamp | D-/B-Number |
---|---|---|---|---|---|
Declarations of Conformity | UKCA - isoxx425 | 142.1 KB | 2022/12/20 05:59:4420.12.2022 05:59:44 | ||
CE Declarations of Conformity | isoXX425 | 151.9 KB | 2023/01/09 06:50:5109.01.2023 06:50:51 | ||
Quickstarts | isoGEN423 | 899.0 KB | EN | 2021/03/18 13:27:2518.03.2021 13:27:25 | D00221 |
Manuals | isoGEN423 | 2.4 MB | EN | 2021/04/20 08:09:2720.04.2021 08:09:27 | D00221 |
Datasheets | isoGEN423 | 385.5 KB | EN | 2022/06/09 10:54:3709.06.2022 10:54:37 | D00221 |